C00056 | torque, C00057 | maximum torque, C00058 | output frequency – Lenze 8400 TopLine User Manual
Page 898: C00059 | appl.: reference frequency c11, C00060 | motor rotor position, C00058, C00056/2, C00057, Is dire, C00059
17
Parameter reference
17.2
Parameter list | C00056
898
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00056
C00057
C00058
C00059
C00060
Parameter | Name:
C00056 | Torque
Data type: INTEGER_32
Index: 24519
d
= 5FC7
h
Display of the current torque
Display range
(min. value | unit | max. value)
-65000.00
Nm
65000.00
Subcodes
Info
C00056/1
Torque demand
• Only in case of sensorless vector control (
) and
servo control (
).
C00056/2
Actual torque value
• Estimated actual torque for all motor control modes.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00057 | Maximum torque
Data type: UNSIGNED_32
Index: 24518
d
= 5FC6
h
Display of the maximum torque to be generated by the motor
• The maximum torque to be generated by the motor depends on various factors, e.g. on Imax in motor mode
(
) and the motor type used.
Display range
(min. value | unit | max. value)
0.00
Nm
65000.00
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00058 | Output frequency
Data type: INTEGER_32
Index: 24517
d
= 5FC5
h
Display of the current output frequency
Display range
(min. value | unit | max. value)
-1300.00
Hz
1300.00
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00059 | Appl.: Reference frequency C11
Data type: UNSIGNED_32
Index: 24516
d
= 5FC4
h
Display of the field frequency which corresponds to the reference speed set in
Display range
(min. value | unit | max. value)
0.00
Hz
1300.00
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00060 | Motor rotor position
Data type: UNSIGNED_16
Index: 24515
d
= 5FC3
h
Display range
(min. value | unit | max. value)
0
2047
Read access Write access CINH PLC STOP No transfer COM MOT