C01191 | ptc characteristic: temperature 1/2, C01192 | ptc characteristic: resistance 1/2, C01193 | motor temp. feedback system – Lenze 8400 TopLine User Manual
Page 1175: C01201 | mck: cycle, C01201/1, Hen the cycle, C01193, C01191/1, C01191/2, C01192/1
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
1175
17
Parameter reference
17.2
Parameter list | C01191
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01191
C01192
C01193
C01201
Parameter | Name:
C01191 | PTC characteristic: Temperature 1/2
Data type: UNSIGNED_8
Index: 23384
d
= 5B58
h
The spec. thermal sensor characteristic is selected through the setting
="1"
Encoder/feedback system: Motor temperature monitoring (KTY)
Setting range
(min. value | unit | max. value)
0
°C
255
Subcodes
Lenze setting
Info
C01191/1
100 °C
PTC characteristic: Temperature 1
C01191/2
150 °C
PTC characteristic: Temperature 2
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01192 | PTC characteristic: Resistance 1/2
Data type: INTEGER_32
Index: 23383
d
= 5B57
h
The spec. thermal sensor characteristic is selected through the setting
="1"
Encoder/feedback system: Motor temperature monitoring (KTY)
Setting range
(min. value | unit | max. value)
0
Ohm
30000
Subcodes
Lenze setting
Info
C01192/1
1070 Ohms
PTC characteristic: Resistance 1
C01192/2
2225 Ohm
PTC characteristic: Resistance 2
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01193 | Motor temp. feedback system
Data type: UNSIGNED_8
Index: 23382
d
= 5B56
h
Selection of the feedback system for monitoring the motor temperature
Encoder/feedback system: Motor temperature monitoring (KTY)
Selection list
(Lenze setting printed in bold)
0 Speed feedback
1 Resolver input
2 Encoder input
5 Res. and enc. parallel
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01201 | MCK: Cycle
Data type: INTEGER_32
Index: 23374
d
= 5B4E
h
Cycle for Modulo measuring system
• When the cycle is set to 0 units (Lenze setting), the traversing range is unlimited (classical measuring system).
Activation of the Modulo measuring system
Setting range
(min. value | unit | max. value)
0.0000
units
214748.3647
Subcodes
Lenze setting
Info
C01201/1
0.0000 units
MCK: Cycle
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10000