Ab01: axis bus timeout [xx.0126.00001, Ab02: axis bus io error [xx.0126.00002, Ce04: mci communication error [xx.0127.00002 – Lenze 8400 TopLine User Manual
Page 718: Ce0f: mci control word [xx.0127.00015, Xx.0126.00001, Xx.0126.00002, Xx.0127.00002, Xx.0127.00015, 10 diagnostics & error management
![background image](/manuals/566308/718/background.png)
10
Diagnostics & error management
10.9
Error messages of the operating system
718
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Ab01: Axis bus timeout [xx.0126.00001]
Ab02: Axis bus IO error [xx.0126.00002]
CE04: MCI communication error [xx.0127.00002]
CE0F: MCI control word [xx.0127.00015]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
axis bus data error monitoring
has been triggered as
the monitoring time for data errors set in
has
been exceeded.
• The current number of incorrectly transmitted
• The current number of incorrectly received telegrams
is displayed in
• The current axis bus error status is displayed in
.
• Check wiring and bus terminating resistor.
• Assign different IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
An axis bus node has put the
into the "error"
status with parameterised "master/slave" function
("release cord" principle).
• In the "Error" status, all nodes start their adjustable
response, e.g. a synchronised braking of the drive
system or the master only brakes the network to
standstill.
Remove the fault of the node which pulled the "release
cord".
Note: The "error" status can only be reset by the node
defined as "master".
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Communication error with extension module in slot 1.
• Eliminate EMC interference.
• Switch off controller, correctly plug in the module,
switch on the controller again.
• Mains switching or restart of the controller,
respectively.
• Replace module/controller.
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Bit 14 ("SetFail") of the wMciCtrl control word of the
system block has been set.
Trace back signal source on the bus (e.g. PROFIBUS) that
sets bit 14 ("SetFail").