7 monitoring, Monitoring, 6encoder/feedback system – Lenze 8400 TopLine User Manual
Page 368
6
Encoder/feedback system
6.7
Monitoring
368
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.7
Monitoring
Parameterisation dialog (cutout)
Parameter
Info
Lenze setting
Value Unit
Open-circuit monitoring
0: Speed encoder and position
encoder
Resp. open circuit HTL encoder
1: Fault
Resp. to MultiEncoder open circuit
1: Fault
Resp. to resolver open circuit
1: Fault
Up to and including version 02.xx.xx:
Resp. to encoder comm. error
1: Fault
From version 12.00.00:
Resp. to encoder pulse deviation
0: No Reaction
Up to and including version 02.xx.xx:
Resp. to encoder pulse deviation
1: Fault
From version 12.00.00:
Resp. to encoder comm. error
1: Fault
Resp. to Hiperface status
6: Information
Resp. to invalid Hiperface position
6: Information
Resp. to SinCos inaccuracy
6: Information
Resp. to max. freq. feedb. DIG12/67
1: Fault
Monitoring of encoder value (LS_MultiEncoder: bFail)
LS_MultiEncoder: Data area min
-214748.3647 units
LS_MultiEncoder: Data area max
214748.3647 units
LS_MultiEncoder: Max. position jump
0.0000 units
LS_MultiEncoder: Information bFail
-
Monitoring of encoder value (LS_Resolver: bFail)
LS_Resolver: Information bFail
-
Highlighted in grey = display parameter