I-1006, I-1014, 12 system bus "can on board – Lenze 8400 TopLine User Manual
Page 808
![background image](/manuals/566308/808/background.png)
12
System bus "CAN on board"
12.11
Implemented CANopen objects | I-1006
808
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1006
Setting the sync telegram cycle time.
• The cycle time can be selected as "1000" or as an integer multiple of it.
• If "0 μs"
is set (Lenze setting), no sync telegrams are created.
• This object relates to code
.
I-1014
When communication errors occur and are acknowledged or when internal errors occur in the
communication module or controller (e.g. "fault"), the system bus sends an error message. The
telegram is sent once for every error. This function can be activated or deactivated with bit 31.
[12-3] Data telegram assignment
Index:
I-1006
Name:
Communication cycle period
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Communication cycle period
0 μs
0
μs
65535000 rw
U32
Index:
I-1014
Name:
COB-ID EMCY
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: COB-ID EMCY
0x80 + node ID
0
4294967295 rw
U32
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31
Bit 30
Bit 29 ... bit 11
Bit 10 ... bit 0
0/1
0
Extended identifier*
11-bit identifier
* The extended identifier is not supported. Bit 11 ... bit 29 must be set to "0".
Bit
Setting
Bit 31
0 Emergency object is valid.
1 Emergency object is invalid.
Note!
The identifier can only be changed in the "emergency object invalid" status (bit 31 = 1).