Page 116: Stop
4
Device control (DCTRL)
4.2
Device state machine and device states
116
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2.3
Ident
The controller has been provided with functions for automatically detecting the motor parameters,
the resolver error and the pole position of a synchronous motor. If such an "identification" is active,
the controller is in the "Ident" status.
The "Ident" device status can only be reached from the "
" device status, i.e. the
controller must be inhibited first so that identification can be started afterwards via the
corresponding device command:
After the identification is completed, the status changes back to "
"DRV-RDY" LED
"DRV-ERR" LED
Display in status word 1 (
)
Bit 11
Bit 10
Bit 9
Bit 8
OFF
Ident
0
0
1
0
Device command
Function
Detailed information
Motor parameter identification
Automatic motor parameter identification
Identify resolver error
e
Identify pole position (360°)
Stop!
During the identification of the motor parameters or the pole position, the controller
does not respond to setpoint changes or control processes (e.g. speed setpoints, quick
stop, torque limitations).
While an identification is being executed,
• the application remains active,
• all system interfaces (IO, bus systems, etc.) remain active,
• error monitoring remains active,
• the inverter is controlled independently of the setpoint sources.