C00105 | decel. time - quick stop, C00106 | auto dcb: hold time, C00107 | dc braking: hold time – Lenze 8400 TopLine User Manual
Page 910: C00105, Time parameterised in, C00106, C00107, Has expire, Fter the hold time, 17 parameter reference
17
Parameter reference
17.2
Parameter list | C00105
910
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00105
C00106
C00107
Parameter | Name:
C00105 | Decel. time - quick stop
Data type: UNSIGNED_32
Index: 24470
d
= 5F96
h
The set deceleration time determines the ramp slope at quick stop
Activate/deactivate quick stop
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.900 2.000 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00106 | Auto DCB: Hold time
Data type: UNSIGNED_32
Index: 24469
d
= 5F95
h
Hold time of the automatic DC injection brake
• The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.000 0.500 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00107 | DC braking: Hold time
Data type: UNSIGNED_32
Index: 24468
d
= 5F94
h
Maximum hold time of the manual DC injection brake
• A time can be set here after which the DC injection brake is switched off automatically to prevent the motor from
thermal overload.
• When "999.000 s" is set, the hold time is infinite.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.000 999.000 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000