C00034 | ainx: configuration, C00036 | dc braking: current, C00036 – Lenze 8400 TopLine User Manual
Page 895: Meterised in, Is i, C00034/1, C00034/2, C00034, C00034/x, 17 parameter reference
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
895
17
Parameter reference
17.2
Parameter list | C00034
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00034
C00036
Parameter | Name:
C00034 | AINx: Configuration
Data type: UNSIGNED_8
Index: 24541
d
= 5FDD
h
Configuration of the analog inputs for current or voltage measurement
Selection list
Info
0 -10V..+10V
Input signal is the voltage signal -10 V ... +10 V
• -10 V ... +10 V ≡ -100 % ... +100 %
1 0mA..20mA
Input signal is the current signal 0 mA ... 20 mA
• 0 mA ... 20 mA ≡ 0 % ... +100 %
2 4mA..20mA
Input signal is the current signal 4 mA ... 20 mA
• 4 mA ... 20 mA ≡ 0 % ... +100 %
• The current loop is monitored for open circuit
(I < 4 mA) by the device.
Subcodes
Lenze setting
Info
C00034/1
0: -10V..+10V
AIN1: Config.
C00034/2
0: -10V..+10V
AIN2: Config.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00036 | DC braking: Current
Data type: INTEGER_16
Index: 24539
d
= 5FDB
h
Braking current in [%] based on rated device current (
)
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
200.00 50.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100