Parameter list | C00571
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00571
C00572
C00574
C00576
Parameter | Name:
C00571 | Resp. to wrong controller setting
Data type: UNSIGNED_8
Index: 24004
d
= 5DC4
h
From version 14.00.00
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes
Lenze setting
Info
C00571/1
6: Information
Resp. to: Motor control does not match motor data
C00571/2
1: Fault
Resp. to a non-set speed controller
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00572 | Brake resistor overload threshold
Data type: UNSIGNED_8
Index: 24003
d
= 5DC3
h
Adjustable threshold for monitoring the brake resistor utilisation
• The response for reaching the threshold can be selected in
.
Setting range
(min. value | unit | max. value)
Lenze setting
0
%
100 100 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00574 | Resp. to brake resist. overtemp.
Data type: UNSIGNED_8
Index: 24001
d
= 5DC1
h
Response which is triggered if the threshold set in
for monitoring brake resistor utilisation is reached.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00576 | SC: Optimisation of field feedforward control
Data type: UNSIGNED_16
Index: 23999
d
= 5DBF
h
Point of action of the direct-axis current setpoint precontrol for an early reduction of the field current. In this way,
the acceleration behaviour can be improved in the field weakening range.
• The entry [%] refers to the slip of the asynchronous motor.
Setting range
(min. value | unit | max. value)
Lenze setting
0
%
600 200 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1