Ca0f: can control word [xx.0131.00015, Ce1: can rpdo1 [xx.0135.00001, Ce2: can rpdo2 [xx.0135.00002 – Lenze 8400 TopLine User Manual
Page 720: Ce3: can rpdo3 [xx.0135.00003, Cp04: can rpdo4 [xx.0135.00004, Xx.0131.00015, Xx.0135.00001, Xx.0135.00002, Xx.0135.00003, Xx.0135.00004
![background image](/manuals/566308/720/background.png)
10
Diagnostics & error management
10.9
Error messages of the operating system
720
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CA0F: CAN control word [xx.0131.00015]
CE1: CAN RPDO1 [xx.0135.00001]
CE2: CAN RPDO2 [xx.0135.00002]
CE3: CAN RPDO3 [xx.0135.00003]
CP04: CAN RPDO4 [xx.0135.00004]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Bit 14 ("SetFail") in the wCANControl control word of the
system block has been set.
Trace back signal source on the CAN bus that sets bit 14
("SetFail").
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: Time monitoring for RPDO1 has been
triggered.
• RPDO1 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: Time monitoring for RPDO2 has been
triggered.
• RPDO2 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: Time monitoring for RPDO3 has been
triggered.
• RPDO3 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: Time monitoring for RPDO4 has been
triggered.
• RPDO4 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.