9basic drive functions (mck) – Lenze 8400 TopLine User Manual
Page 571
![background image](/manuals/566308/571/background.png)
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
571
9
Basic drive functions (MCK)
9.3
MCKInterface
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Control of the Motion Control Kernel
Control of the basic drive functions implemented in the Motion Control Kernel is carried out by
means of
• direct specification of the control words, for example via a master control unit also connected
to the fieldbus.
• For this purpose, the control word inputs can be directly connected to the field bus interface
LP_MciIn respectively LP_CanIn.
• See the "
" chapter for a detailed description of the individual control bits.
• the specification of individual process signals at the
FB which are then ORed
with the control word.
Plausibility check
The process signals applied to the
FB are logically linked by means of an OR logic
operation to the specified control word via the two control word inputs wInMckPosCtrl_1 and
wInMckPosCtrl_2 and, after a plausibility check, are output via the two control word outputs
wOutMckPosCtrl_1 and wOutMckPosCtrl_2 .
• The profile number, the operating mode, and the positioning mode are checked for plausibility.
• If implausibility is detected, only control bit information is output and the bFail output is set to
TRUE.
• The result of the plausibility check is provided as the wFailState output word and displayed in
.
The control words that are output, namely wOutMckPosCtrl_1 and wOutMckPosCtrl_2, constitute
the input information for the
Status information of the Motion Control Kernel
Output by the
, the status words wMotionState1 and wMotionState2 also
constitute input information for the downstream
FB, which provides this
information to the application in the form of process signals.