C00498
Parameter | Name:
C00498 | Open-circuit monitoring
Data type: UNSIGNED_8
Index: 24077
d
= 5E0D
h
Configuration of open-circuit monitoring for encoder/feedback system
• We recommend using the Lenze setting.
• The settings 1 ... 3 make sense if the respective encoder is not to be used as speed encoder or position encoder
but within the scope of the application. Moreover, a directed disconnection of the monitoring is possible.
Selection list
Info
0 Speed and position encoder
Open-circuit monitoring is active for the speed encoder
and the position encoder selected in
• Depending on whether a speed encoder or position
encoder has been selected, the monitoring mode for
the resolver and/or encoder is activated.
• If no speed encoder and position encoder have been
selected, open-circuit monitoring is deactivated.
1 Resolver only
Open-circuit monitoring is only active for the resolver,
independent on the selection of the speed encoder and
position encoder.
• Open-circuit monitoring for the encoder is
deactivated.
2 Encoder only
Open-circuit monitoring is only active for the encoder,
independent on the selection of the speed encoder and
position encoder.
• Open-circuit monitoring for the resolver is
deactivated.
3 Resolver and encoder
Open-circuit monitoring is active for the resolver and
encoder, independent on the selection of the speed
encoder and position encoder.
Subcodes
Lenze setting
Info
C00498/1
0: Speed encoder and position
encoder
Open-circuit monitoring
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1