2 hardware limit switch, Hardware limit switch, Negativ – Lenze 8400 TopLine User Manual
Page 592: 9basic drive functions (mck), Stop
9
Basic drive functions (MCK)
9.4
Basic settings
592
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.4.3.2
Hardware limit switch
The travel range limits are monitored by means of limit switches via the inputs bLimitSwitchPos and
bLimitSwitchNeg of the
system block.
• The two inputs react to the TRUE state.
• In
, the two inputs are connected to the digital inputs provided for
connection of the limit switches.
Behaviour when hardware limit switches are active
If one of the two monitoring inputs is set to TRUE:
• The error response "TroubleQuickStop" takes place in the Lenze setting, i.e. the drive is brought
to a standstill in the deceleration time set for the quick stop function and does so irrespective of
the setpoint selection. The error response can be parameterised in
and
• The error message "Ck01: Pos. HW limit switch" or. "Ck02: Neg. HW limit switch" is entered in
the logbook.
• Bit 10 ("Pos. HW-Limit Detected") or bit 11 ("Neg. HW-Limit Detected") is set in the
.
• Depending on the parameterised fault response, the drive cannot traverse until the error has
been acknowledged.
Stop!
The limit switches are only evaluated if the limit switches for the respective operating
mode have been activated (see the following table)!
Operating mode
Hardware limit switch effective
Yes (adjustable in
- bit 2)
Depending on the selected homing mode (see description of the homing modes)
No (adjustable in
- bit 2)
Yes
Yes
Yes (adjustable in
- bit 2)
Note!
If the digital inputs used for connecting the limit switches are fail-safe inputs (tripping
at LOW level), you simply change the terminal polarity of the corresponding digital
Note!
An activated limit switch can be retracted again by manual jog in the opposed direction
or with the "Retract limit switch" function.
Retracting of an operated limit switch
Only in the "
" operating mode, retracting of the limit switch resets bit 10
("Pos. HW-Limit Detected") or bit 11 ("Neg. HW-Limit Detected") in the