5motor control (mctrl) – Lenze 8400 TopLine User Manual
Page 251
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
251
5
Motor control (MCTRL)
5.9
Servo control (SC)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Field controller
The field controller is designed as a PI controller.
The gain Vp (
) of the field controller can be calculated using the motor rotor time constant
and the equivalent time constant of the current-controlled motor:
If the rated data of the motor and the mass inertia of the drive system are known, we recommend
the following setting:
[5-18] Recommendation for the setting of the gain and the time constant of the field controller
Tip!
The motor rotor time constant depends on the motor rotor resistance, the magnetising
inductance, and the leakage inductance.
• For an optimal calculation, we recommend to select the motor from the motor catalogue
of the »Engineer« first if a Lenze motor is used.
Selecting a motor from the motor
• If a third party manufacturer's motor is used, motor parameter identification must be
Automatic motor data identification
Parameter
Info
Lenze setting
Value Unit
SC: Vp field controller
12.80
SC: Tn field controller
256.0 ms
V
PField
: Gain of the field controller (
T
R
: Motor rotor time constant (
)
T
Equivalent
: Motor equivalent time constant (approx. 2.5 ms)
a: Measure for damping (z. B. a = 2)
V
PField
: Gain of the field controller (
T
R
: Motor rotor time constant (
)
T
Equi
: Motor equivalent time constant
T
NField
: Time constant of the field controller (
)
V
PFeld
T
R
s
[ ]
a
2
T
Replacement
ms
[
]
⋅
------------------------------------------------------
%
[ ]
=
V
PFeld
T
R
s
[ ]
4 T
Replacement
ms
[
]
⋅
---------------------------------------------------
T
R
s
[ ]
0.01 s
[ ]
-------------------
=
≈
T
NFeld
ms
[
]
T
R
ms
[
]
=