5motor control (mctrl) – Lenze 8400 TopLine User Manual
Page 253
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
253
5
Motor control (MCTRL)
5.9
Servo control (SC)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Field feedforward control
To have enough voltage reserve available for dynamic acceleration processes, a timely weakening
of the field is required. The field weakening is controlled by the field feedforward control.
The field feedforward control reciprocally reduces the magnetising current from the V/f base
) on. The starting point of the reduction can be shifted to low frequencies via the
field feedforward control (
). Thus, more voltage reserve is available for acceleration
processes.
The field feedforward control (
) must be specified in %, based on the rated slip of the
machine.
Tip!
Generally, the Lenze setting is sufficient for most applications.
• We recommend to increase the field feedforward control for applications with very
dynamic acceleration processes in the field weakening range.
• Reduce the field feedforward control for very slow applications if necessary.
Parameter
Info
Lenze setting
Value Unit
SC: Field feedforward control
200.0 %
Note!
The function of the field feedforward control and thus the field weakening control
requires a correct setting of the V/f base frequency (
• The selection of the motor from the »Engineer« motor catalogue and the motor
parameter identification serve to set the V/f base frequency correctly.
• When third-party motors are entered, either the V/f base frequency (
) has to
be calculated manually or a motor parameter identification has to be carried out.
Adapting the V/f base frequency
Automatic motor data identification
Due to an error in the device software, the field feedforward control of the servo control
only operates properly if the V/f base frequency (
) is reduced by the following
factor after being set:
• 400-V devices: Factor 0.173
• 230-V devices: Factor 0.34
The same factor has to be considered for the field feedforward control (
From version 14.00.00
, the control parts can be called for an optimum jerk-free
transition to the field weakening range in a 500-
μ
s cycle. For this purpose, bit 5 has to be
set to "1" int in
.
• With this setting,
do not have any influence anymore on the field
feedforward control.
• We recommend this setting for new applications.