Ou: dc bus overvoltage [xx.0123.00014, Lu: dc bus undervoltage [xx.0123.00015, Oc1: power section - short circuit [xx.0123.00016 – Lenze 8400 TopLine User Manual
Page 709: Message, Lu: undervoltage in the dc bus, Lu: dc bus undervoltage, Xx.0123.00015, Xx.0123.00016, Xx.0123.00014, 10 diagnostics & error management
![background image](/manuals/566308/709/background.png)
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
709
10
Diagnostics & error management
10.9
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
oU: DC bus overvoltage [xx.0123.00014]
LU: DC bus undervoltage [xx.0123.00015]
oC1: Power section - short circuit [xx.0123.00016]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has detected an overvoltage in the DC bus. To
protect the device hardware, the inverter control is
switched off.
• Depending on the configuration of the auto-start lock
function, set
so that, when this error is
tripped, the controller only restarts after the
controller inhibit has been switched.
• If this error message remains active longer than the
time set in
, a "Fault" is tripped. Otherwise, the
deactivation of the error message causes the inverter
control to be enabled again
• In case of the control types VFCplus and SLVC, the
motor voltage is approached to the voltage
setpoint alongside a ramp.
•
From version 15.00.00
, this voltage ramp can be set
in
. If the described remedies are not
possible or do not have any effect, it may be
required to increase this voltage ramp as otherwise
an overcurrent interruption may be caused. This
only happens in case of high motor power and
mass inertia so that the Lenze setting of 1 s should
be sufficient in the majority of cases.
• Reduce load in generator mode.
• Use a brake resistor.
• Use a regenerative power supply unit.
• Establish a DC-bus connection.
• Select a braking method in
which stops the
ramp function generator when reaching the brake
chopper threshold ("HlgStop").
• In case of servo control (SC), set the speed controller
parameters correctly.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has detected a DC bus undervoltage. The
inverter control is switched off because the drive
properties of the motor control cannot be provided
anymore due to the DC bus undervoltage.
• Depending on the configuration of the auto-start lock
function, set
so that, when this error is
tripped, the controller only restarts after the
controller inhibit has been switched.
• Switch on mains supply or ensure sufficient supply via
DC bus.
• Adjust setting in
if required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has recognised a short circuit of the motor
phases. To protect the device electronics, the inverter
control is switched off.
• Mostly, incorrectly executed motor connections are
the cause.
• If the device is inappropriately dimensioned with
regard to the motor load and the current limitation in
the controller (Imax controller) is set incorrectly, this
error message may also occur.
Motor control: Defining current limits
• Check motor connections and the corresponding plug
connector on the device.
• Only use permissible combinations of device power
and motor power.
• Do not set the dynamics of the current limitation
controller too high.