12 braking operation/brake energy management, Braking operation/brake energy management, 5motor control (mctrl) – Lenze 8400 TopLine User Manual
Page 281
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
281
5
Motor control (MCTRL)
5.12
Braking operation/brake energy management
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.12
Braking operation/brake energy management
When braking electrical motors, the kinetic energy of the drive train is fed back regeneratively to the
DC bus. This energy results in a boost of the DC-bus voltage.
• Several different strategies can serve to avoid DC-bus overvoltages:
• Use of a brake resistor
• Stopping of the ramp function generator if brake chopper threshold exceeded (RFG_Stop)
• Use of the "Inverter motor brake" function
• Combination of the above named options
• In the case of inverters with a 3-phase supply, the following is also possible:
• Coupling of the inverters in a DC-bus connection
• Recovery of regenerative energy with a regenerative module
Stop!
If the connected brake resistor is smaller than required, the brake chopper can be
destroyed!
• Appropriate protective measures are described in subchapter "
overload of the brake resistor
If no brake resistor or regenerative module is used, the overvoltage switch-off ("
respond, e.g. in case of short deceleration times during feedback operation.
messages of the operating system