5.10.9
Field weakening for synchronous motors
This function extension is available from version 02.00.00!
[5-25] Voltage/speed characteristic with switched-on field weakening
[5-26] Calculation of the maximally reachable speed with switched-on field weakening
Note!
Function only possible with:
• Servo control (SC)
• Sensorless control for synchronous motors (SLPSM)
(from version 10.00.00)
In the Lenze setting, the field weakening for synchronous motors is activated in
.
• If a high energy efficiency is required, keep the field weakening switched off or restrict
the field weakening operation via
Stop!
In the field weakening operation, a current is injected into the synchronous motor even
in idle state which can rise to maximum current (
Ensure that this no-load current does not cause the motor to be heated impermissibly!
• The use of a temperature feedback via KTY is recommended.
Armature control range
Field weakening range
• When field weakening is switched on, the motor
magnetising current is increased from 0 A to the maximally
effective magnetising current via an internal control loop
when the voltage limit is reached.
• As a result, a higher speed can be reached at the same
motor voltage or DC-bus voltage.
n
U
motor
n
max
n
nenn_mot
800V
2 U
nenn_mot
⋅
--------------------------------------
⋅
=