7i/o terminals – Lenze 8400 TopLine User Manual
Page 420
![background image](/manuals/566308/420/background.png)
7
I/O terminals
7.5
Configuring exception handling of the output terminals
420
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.5
Configuring exception handling of the output terminals
Exception handling for the analog and digital output terminals in the event of an error can be set
via decoupling configuration and decoupling values.
• Bit coded selection is carried out in
for the analog output terminals, defining the events
that will trigger decoupling.
• Bit coded selection is carried out in
for the digital output terminals, defining the events
that will trigger decoupling.
Finally, the following parameters define the value/status that the output terminals are to have
when they are decoupled:
Related topics:
Configuring exception handling of the CAN PDOs
Bit
Event
Bit 0 SafeTorqueOff
Bit 1 ReadyToSwitchOn
Bit 2 SwitchedOn
Bit 3 Reserved
Bit 4 Trouble
Bit 5 Fault
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Fail CAN_Management
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
Parameter
Info
Lenze setting
Value Unit
AOut1_U: Decoupling value
0.00 %
AOut2_U: Decoupling value
0.00 %
AOut1_I: Decoupling value
0.00 %
AOut2_I: Decoupling value
0.00 %
DigOut decoupling value
Bit coded