5.4.3.3
Optimising the Imax controller
Using the Lenze setting of the current limitation controller, the drive is stable:
Most applications do not require optimisation.
The setting of the current limitation controller must be adapted if
• power control including great moments of inertia is performed.
• Recommendation: Increase of the reset time Ti (
max
controller.
• vibrations occur in the V/f control (VFCplus + encoder) mode during the intervention of the
current limitation controller.
• Recommendation: Increase of the reset time Ti (
max
controller.
• overcurrent errors (e.g. OC3) occur due to load impulses or too high acceleration ramps.
• Recommendation: Reduction of the gain Vp (
) and reset time Ti (
I
max
controller.
Parameter
Info
Lenze setting
Value Unit
VFC: Vp Imax controller
0.25
VFC: Ti Imax controller
65 ms