C00271 | sc: width of current setpoint filter, C00272 | sc: depth of current setpoint filter, C00273 | moment of inertia motor – Lenze 8400 TopLine User Manual
Page 945: C00274 | sc: max. change in acceleration, C00275 | filter setpoint feedforward control, C00273, C00274, C00275, Under, And repe
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
945
17
Parameter reference
17.2
Parameter list | C00271
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00271
C00272
C00273
C00274
C00275
Parameter | Name:
C00271 | SC: Width of current setpoint filter
Data type: UNSIGNED_16
Index: 24304
d
= 5EF0
h
Frequency width of the current setpoint filter at servo control (
) and sensorless control for synchronous motors
(
)
• Width around the frequency to be inhibited (
).
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
Hz
500.0 0.0 Hz
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00272 | SC: Depth of current setpoint filter
Data type: UNSIGNED_16
Index: 24303
d
= 5EEF
h
Damping of the current setpoint filter at servo control (
) and sensorless control for synchronous motors (
Setting range
(min. value | unit | max. value)
Lenze setting
0
dB
100 0 db
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00273 | Moment of inertia motor
Data type: UNSIGNED_32
Index: 24302
d
= 5EEE
h
Moment of inertia for setpoint feedforward control at servo control (
) and sensorless vector control (
)
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
kg cm^2
6000000.00 0.00 kg cm^2
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00274 | SC: Max. change in acceleration
Data type: UNSIGNED_16
Index: 24301
d
= 5EED
h
Limitation of the acceleration change at servo control (
) and sensorless control for synchronous motors (
• Setting in % of M_Nenn per ms.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%/ms
400.0 400.0 %/ms
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00275 | Filter setpoint feedforward control
Data type: UNSIGNED_16
Index: 24300
d
= 5EEC
h
Filter time of setpoint feedforward control at servo control (
) and sensorless vector control (
)
• The setpoint feedforward control requires the entry of the moment of inertia in
.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
ms
1000.0 1.0 ms
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10