1123
17
Parameter reference
17.2
Parameter list | C00915
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00915
C00916
C00917
C00918
Parameter | Name:
C00915 | Motor cable length
Data type: UNSIGNED_16
Index: 23660
d
= 5C6C
h
Single motor cable length for calculating the motor cable resistance
• The calculated motor cable resistance is displayed in
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
m
1000.0 5.0 m
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00916 | Motor cable cross-section
Data type: UNSIGNED_16
Index: 23659
d
= 5C6B
h
Motor cable cross-section of a phase/cable for calculating the motor cable resistance
• The calculated motor cable resistance is displayed in
Setting range
(min. value | unit | max. value)
Lenze setting
0.50
mm^2
100.00 6.00 mm^2
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00917 | Motor cable resistance
Data type: UNSIGNED_16
Index: 23658
d
= 5C6A
h
Display of the motor cable resistance of a motor cable phase
• The motor cable resistance is calculated from the motor cable length set in
and the motor cable cross-
Display range
(min. value | unit | max. value)
0
mOhm
64000
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00918 | SC: Start motor magnetising current
Data type: UNSIGNED_8
Index: 23657
d
= 5C69
h
If the servo control (
) mode is selected and the controller is enabled, the speed setpoint for motor control will only
be enabled when the motor magnetising current has reached the threshold value set here.
• The adjustable percentage threshold value refers to the rated magnetising current (
Setting range
(min. value | unit | max. value)
Lenze setting
0
%
90 87 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1