1 adapting the v/f base frequency, Adapting the v/f base frequency, Adapting the v/f base frequency ( 164) – Lenze 8400 TopLine User Manual
Page 164: 5motor control (mctrl)
5
Motor control (MCTRL)
5.4
V/f characteristic control (VFCplus)
164
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4.3.1
Adapting the V/f base frequency
The V/f base frequency (
) determines the slope of the V/f characteristic and has
considerable influence on the current, torque, and power performance of the motor.
applies to all permitted mains voltages.
• Mains fluctuations or fluctuations of the DC-bus voltage (operation in generator mode) do not
need to be considered when the V/f base frequency is set. They are automatically compensated
for by the internal mains voltage compensation of the device.
• Depending on the setting in
, it may be required to adapt the reference speed (
)
to traverse the entire speed range of the motor.
• The V/f base frequency is automatically calculated from the stored motor nameplate data by
the motor parameter identification:
[5-4]
Calculation of the V/f base frequency
Typical values of the V/f base frequency
V
FI
: Mains voltage 400 V or 230 V
V
ratedmot
: Rated motor voltage depending on the connection method
f
rated
: Rated motor frequency
C00015 [Hz]
U
FI
[V]
U
Ratedmot
[V]
----------------------------------
f
Rated
Hz
⋅
=
Drive controller with 400 V mains connection
Motor voltage [V]
Motor frequency [Hz]
Motor connection
V/f base frequency
(C00015)
230 / 400
50
50 Hz
220 / 380
50
52.6 Hz
280 / 480
60
50 Hz
400 / 690
400
50
50
50 Hz
230 / 400
280 / 480
400
50
60
87
87 Hz
220 / 380
50
90.9 Hz
Drive controller with 230 V mains connection
Motor voltage [V]
Motor frequency [Hz]
Motor connection
V/f base frequency
(C00015)
230
50
50 Hz
220 / 380
50
52.3 Hz