19.1.71
L_Curve_1
This FB can optionally display a characteristic function or a curve function y=f(x), the X axis being
the input signal and the Y axis being the output signal.
• A limitation of the input value can be set in
(upper limit) and
(lower limit).
• The output value is internally limited to ±199.99 %. If a limitation of the output value is active,
bLimit is set to TRUE.
Inputs
Outputs
Parameter
Identifier
Data type
Information/possible settings
nIn_a
INT
Input value (x)
• ±16384 ≡ ±100 %
• A limitation of the input value can be set in C00961/1 (upper limit) and C00961/2
(lower limit).
Identifier
Data type
Value/meaning
nOut_a
INT
Output value (y)
• ±16384 ≡ ±100 %
• Internal limitation to ±32767 (±199.99 %)
bLimit
BOOL
"Limitation active" status signal
TRUE The output value is limited to ±199.99 %.
Parameter
Possible settings
Info
From version 02.00.00
-199.99
%
199.99 Output value
• Read only
Function selection
0 Out = 0
FB deactivated (Lenze setting)
1 Out = In
2 Out = f(In)
In preparation!
3 Out = f(table)
-199.99
%
199.99 Upper limit for input value
• Lenze setting: 199.99 %
-199.99
%
199.99 Lower limit for input value
• Lenze setting: -199.99 %