System bus "CAN on board"
12.9
Parameter data transfer
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.9.2.3
Data 1 ... Data 4
Maximally 4 bytes are available for parameter value entries. Depending on the data format, they are
assigned as follows:
Example
A value of "123.45" is to be transmitted for a code, unit: "%" (e.g. C00039/1: "Fixed setpoint-JOG1").
In controllers of the 8400 series, parameters with the "%" unit have two decimal positions and hence
a scaling factor of "100".
Calculation:
• Value to be transmitted = scaling factor x value
• Data
(1 ... 4)
= 100 x 123.45 = 12345 (0x00 00 30 39)
Entries:
1st byte
2nd byte 3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
LOW byte
HIGH
byte
LOW word
HIGH word
LOW byte
HIGH byte
LOW byte
HIGH byte
5th byte
6th byte
7th byte
8th byte
Parameter value (1 byte)
0x00
0x00
0x00
Parameter value (2 bytes)
0x00
0x00
LOW byte
HIGH byte
Parameter value (4 bytes)
LOW word
HIGH word
LOW byte
HIGH byte
LOW byte
HIGH byte
Note!
The "Factor" column of the
contains a so-called scaling factor for all
Lenze parameters. The scaling factor is relevant to the transfer of parameter values
which have one or more decimal positions in the parameter list.
If the scaling factor is > 1, the value must be multiplied by the indicated scaling factor
prior to transmission to be able to transfer the value as an integer. At the SDO client end,
the integer must be divided by the scaling factor to obtain the original value including
decimal positions again.
1st byte
2nd byte 3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
0x39
0x30
0x00
0x00