4 parameter setting, Parameter setting, 14 axis bus – Lenze 8400 TopLine User Manual
Page 841
![background image](/manuals/566308/841/background.png)
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
841
14
Axis bus
14.2
Data transfer axis bus
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.2.4
Parameter setting
Short overview of the relevant parameters:
Parameter
Info
Lenze setting
Value Unit
Sync signal source
0: Off
Axis bus address
• 0 ≡ Node is disconnected from the axis bus
• 1 ≡ Master
• 2 ... 62 ≡ slave 1 ... slave 61
0
Axis bus no. of nodes
• Number of controllers connected to the axis
bus.
2
Axis bus decel. boot-up
3000 ms
Axis bus decel. BusOffRecovery
1000 ms
Axis bus monitoring time
1000 ms
Axis bus IO function
0: Off
Configuring exception handling of the received data
Decoupling inputs from the axis bus
•
From version 12.00.00
0x0000
Decoupling values
•
From version 12.00.00
0
Axis bus data error monitoring
Resp. to axis bus data error
•
From version 12.00.00
1: Fault
Diagnostic parameter
Axis bus status
• Display whether the node participates in the
axis bus data exchange (PDO active) or is
only switched on passively to the axis bus
(PDO stopped).
-
Axis bus error status
-
Axis bus MessageError
-
Axis bus Tx_Error
•
From version 12.00.00
• Error counter for faulty sent telegrams.
-
Axis bus Rx_Error
•
From version 12.00.00
• Error counter for faulty received telegrams.
-
Axis bus transmitting meter
•
From version 12.00.00
• Display of the entire number of sent
telegrams
-
Axis bus receiving meter
•
From version 12.00.00
• Display of the entire number of received
telegrams.
-
Highlighted in grey = display parameter