C00020 | ain2: characteristic, C00021 | slip comp, C00022 | imax in motor mode – Lenze 8400 TopLine User Manual
Page 892: C00023 | imax in generator mode, C00022, C00021, Mpensation, C00023, Motor mode, For generator load set in
17
Parameter reference
17.2
Parameter list | C00020
892
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00020
C00021
C00022
C00023
Parameter | Name:
C00020 | AIN2: Characteristic
Data type: INTEGER_16
Index: 24555
d
= 5FEB
h
Signal adaptation via characteristic
Setting range
(min. value | unit | max. value)
0.00
%
199.99
Subcodes
Lenze setting
Info
C00020/1
0.00 %
AIN2: (+y0) = min
C00020/2
0.00 %
AIN2: (+x0) = Dead band
C00020/3
0.00 %
AIN2: (-y0) = (-min)
C00020/4
0.00 %
AIN2: (-x0) = (-Dead band)
C00020/5
100.00 %
AIN2: (+ymax)
C00020/6
100.00 %
AIN2: (+xmax)
C00020/7
100.00 %
AIN2: (-ymax)
C00020/8
100.00 %
AIN2: (-xmax)
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00021 | Slip comp.
Data type: INTEGER_16
Index: 24554
d
= 5FEA
h
Slip compensation for V/f characteristic control (
) and sensorless vector control (
• A higher slip compensation results in a higher increase in frequency and voltage when the machine is under load.
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Optimising the operational performance by slip compensation
Setting range
(min. value | unit | max. value)
Lenze setting
-100.00
%
100.00 2.67 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00022 | Imax in motor mode
Data type: UNSIGNED_16
Index: 24553
d
= 5FE9
h
Maximum current in motor mode for all motor control modes
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
A
655.35 47.00 A
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00023 | Imax in generator mode
Data type: INTEGER_16
Index: 24552
d
= 5FE8
h
Maximum current in generator mode for all motor control modes
• 100 % ≡ Imax in motor mode (
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
100.00 100.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100