C00161
C00162
C00163
Parameter | Name:
C00161 | LS_SetError_x: Error number
Data type: UNSIGNED_16
Index: 24414
d
= 5F5E
h
Setting of the error number for user error messages
Setting range
(min. value | unit | max. value)
0
65535
Subcodes
Lenze setting
Info
C00161/1
1
: Error no.1
C00161/2
2
: Error no.2
C00161/3
3
: Error no.3
C00161/4
4
: Error no.4
C00161/5
1
: Error no.1
C00161/6
2
: Error no.2
C00161/7
3
: Error no.3
C00161/8
4
: Error no.4
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00162 | Error number masked
Data type: UNSIGNED_32
Index: 24413
d
= 5F5D
h
From version 13.00.00
Display of the 32-bit error number of the status determining error without error type
• The error number displayed here only contains the error subject area and error ID (lower 26 bits of the 32-bit error
number)
Structure of the 32-bit error number (bit coding)
Display range
(min. value | unit | max. value)
0
4294967295
Subcodes
Info
C00162/1
Subject area + Id statuserror
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00163 | Logbook - binary elements
Data type: UNSIGNED_16
Index: 24412
d
= 5F5C
h
Selection of two binary signals to be logged in the logbook
Selection list
Info
0 No signal
1 DI1: Input signal
2 DI2: Input signal
3 DI3: Input signal
4 DI4: Input signal
5 Controller inhibit signal
6 Digital counter: Comparison bit
7 CAN1 input bit 0
8 CAN1 input bit 1
9 CAN1 input bit 2
10 CAN1 input bit 3