1 function 1: on-delay, 2 function 2: off-delay, 5function blocks – Lenze E94A User Manual
Page 580

5
Function blocks
5.167
L_TbDelay - delay
580
Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.167.1
Function 1: ON-delay
Selection: C04010 = "0" (Lenze setting)
• In this mode, the FB operates like a retriggerable monoflop.
Functional sequence
1. A FALSE-TRUE edge at bIn starts the internal timing element ().
2. After the delay time set via C04011 has elapsed, bOut is set to TRUE.
3. A TRUE-FALSE edge at bIn sets bOut to FALSE again. Simultaneously, the internal timing element
is reset.
5.167.2
Function 2: OFF-delay
Selection: C04010 = "1"
Functional sequence
1. A FALSE-TRUE edge at bIn sets bOut to TRUE. Simultaneously, the internal timing element () is
reset.
2. A TRUE-FALSE edge at bIn starts the internal timing element.
3. After the delay time set via C04011 has elapsed, bOut is reset to FALSE.
= internal timing element
TRUE
FALSE
bOut
t
TRUE
FALSE
bIn
t
C04011
C04011
C04011
t
0
= internal timing element
TRUE
FALSE
bOut
t
TRUE
FALSE
bIn
t
C04011
C04011
C04011
C04011
t
0