L_SdMotorPot - motor potentiometer

492

Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.130.4

Deactivation function

If the control input bDisable is set to TRUE, the control inputs bUp and bDown are deactivated and

the output value dnOut_n is changed according to the deactivation function set in C04362:

C04362

Deactivation function

0

dnOut_n maintains its last value.

1

dnOut_nis increased to 0 % with the deceleration time or increased with the acceleration ti-

me.

2

dnOut_n is decreased to the lower limit value (C04360/2) with the deceleration time

(C04361/2).

3

dnOut_n is increased to the upper limit value (C04360/1) with the acceleration time

(C04361/1).

11

dnOut_n is set to 0 % immediately.

12

dnOut_n is set to the lower limit value (C04360/2) immediately.

13

dnOut_n is set to the upper limit value (C04360/1) immediately.

Note!

If the motor potentiometer function is reactivated and dnOut_n is beyond the limit va-

lues parameterised, dnOut_n is lead to the nearest limit value under consideration of the

acceleration/deceleration time.
This process is independent of the control signals bUp and bDown.