Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05

505

5

Function blocks

5.133

L_SdRampGenerator - ramp function generator - S-ramp

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Parameter

5.133.1

Loading the ramp function generator

By setting bLoadStartValue to TRUE the ramp function generator is loaded with the signal at

dnStartValue_n.

• This value is accepted immediately and output to nOut_n. No s-shape ramp-up or ramp-down

takes place.

• As long as bLoadStartValue = TRUE , the ramp function generator is inhibited.

Parameter

Possible settings

Information

C04340

0.001

s

1000.000 Acceleration / deceleration time

• Initialisation: 1.000 s

C04341

0.001

s

10.000 S-ramp time

• Initialisation: 0.100 s

C04342

As of library V02.02.xx.xx

-200.000

%

200.000 Setpoint at the input

• Display of the dnIn_n input signal.

C04343

As of library V02.02.xx.xx

-200.000

%

200.000 Setpoint at the output

• Display of the dnOut_n output si-

gnal.