5function blocks – Lenze E94A User Manual
Page 289

Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05
289
5
Function blocks
5.79
L_DevWriteParDInt - writing to parameters of the DINT type
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C05923
0
128 Target address
• Selection of parameter channel
for target device.
• Setting is only required if an exter-
nal parameter is to be written
(C05922 > "1").
C05924
0.000
s
10.000 Time-out time
• Time in which the write request
must have been processed.
• Initialisation: 0.000 s
C05925
0.000
s
100.000 Cycle time
• Interval for the cyclic writing of a
parameter.
• Initialisation: 0.000 s
(cyclic writing is deactivated)
Note!
The cycle time set in C05925 applies only to the use of the FB in a 1-ms task! For a longer
task cycle the cycle time is prolonged accordingly:
If the FB is used in the unsolicited task, the cycle time set is not effective. In this case use
an upstream FB
instead, in order to cyclically trigger the write request:
• Connect the output bOut of the FB
with the input bExecute.
• Set the desired cycle time via the parameters of the FB
.
Parameter
Possible settings
Info
Cycle time
C5925 [s] Task cycle [ms]
⋅
1 [ms]
-------------------------------------------------------------------
=