7 action type "waiting, 5function blocks, 7 x x x – Lenze E94A User Manual
Page 446

5
Function blocks
5.114
L_PosSequencer - sequence control
446
Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.114.3.7 Action type "Waiting"
25 actions of type "Waiting" are available for the insertion into the program flow.
• The sequence step is only processed after the waiting time has expired or when the selected
bit 1 ... 32 of the input signal dwDigitalInputs has the selected signal state ("1" or "2") at the time
of processing.
Action call (entry in the sequence table)
with action number xxx = 001 ... 025
Parameter
The available actions 1 ... 25 are indicated via the subcodes 1 ... 25.
Waiting time
Input
Function
C04571
C04572
0
(deactivated)
0
(deactivated)
Sequence step is processed immediately (default setting).
> 0 [s]
0
(deactivated)
After the waiting time has expired, the sequence step will be processed.
> 0 [s]
1 ... 32
The sequence step will be processed when the input for the waiting time has the set
state, but no later than after the set waiting time has elapsed.
0
(deactivated)
1 ... 32
If the input for the waiting function has the set state, the sequence step will be pro-
cessed.
Parameter
Possible settings
Information
C04570/1...25
Text
Comment on waiting step
• Option for description of the func-
tion for keypad/HMI.
C04571/1...25
0 Waiting time is deactivated.
Waiting time
> 0 Waiting time in [s]
C04572/1...25
Input for waiting function
0 Input is deactivated.
1 Sequencer input 1
(Bit 0 of dwDigitalInputs)
2 Sequencer input 2
(Bit 1 of dwDigitalInputs)
... ...
32 Sequencer input 32
(Bit 31 of dwDigitalInputs)
C04573/1...50
Signal state for waiting function
• Only when the input for the wai-
ting function has adopted this
state, the sequence step will be
processed.
0 Sequence step when bit state is "0"
1 Sequence step when bit state is "1"
7 x x x