5.160

L_TbCompare - comparison

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.160

L_TbCompare - comparison

This function block compares two signals of the "DINT" data type and can be used e.g. for implemen-

ting a trigger.

• The comparison function is selected via C04085.
• In contrast to the FB

L_TbCompare_n

, the window and hysteresis of this FB can be adjusted via

inputs instead of parameters.

Inputs

Outputs

Parameter

Function library:

LenzeToolbox

Runtime software licence:

Motion Control HighLevel

Motion Control TopLevel

Identifier/data type

Information/possible settings

dnIn1

DINT

Input signal 1

dnIn2

DINT

Input signal 2

dnTolerance

DINT

Window for comparison operation

• Value is internally limited to ≥0.

dnHysteresis

DINT

Hysteresis for comparison operation

• Value is internally limited to ≥0.

Identifier/data type

Value/meaning

bOut

BOOL

Status signal "Comparison statement is true"

TRUE The statement of the selected comparison mode is true.

Parameter

Possible settings

Information

C04085

Comparison operation

0 dnIn1 = dnIn2

Lenze setting

1 dnIn1 > dnIn2
2 dnIn1 < dnIn2
3 |dnIn1| = |dnIn2|
4 |dnIn1| > |dnIn2|
5 |dnIn1| < |dnIn2|