1 functions, 5function blocks – Lenze E94A User Manual
Page 382

5
Function blocks
5.100
L_LdVirtualMasterV - virtual master for electronic gearboxes
382
Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.100.1
Functions
Handwheel function
• Ensures an easy control of a machine run. The clutched drives are interconnected in a system.
• Incremental encoders via DFIN or multiple encoder input. An input must be selected.
• No ramp functions are active.
• Function is enabled via the control (PLC) by selecting the "handwheel function" operating mode
(C05100 ="2") and setting bEnable to TRUE.
Manual jog (inching)
• Operation per HMI or keys via control (PLC). The locking is done in the PLC.
• Ramp functions are active.
• Parameters are defined once or changed via HMI.
Continuous operation
• Operation per HMI or keys via control (PLC)
• Function starts with a FALSETRUE edge at the bContinuous input. The function remains active
as long as the TRUE level is applied.
• Ramp functions are active.
• The data for production speed are used as parameters.
Synchronise virtual master to the external master
• The virtual master is synchronised to an external speed selection. Thus, the downstream system
can be separated from the external master any time.
• Application: Modular machines: The external speed is delivered by
• MotionBus (Slave) as position selection
• DFIN/multiple encoder input/FB L_LdSetXAxisVelocity (relative synchronism)
• Fieldbus as real encoder as position selection (must be limited to the cycle set).
• The function is activated by setting bEnable to TRUE.
Stop master shaft
• The master shaft is braked to standstill within the operating time set in C05111 setting
bStopInstant to TRUE.
• For this, the enable input bEnable must be set to TRUE.
• This function has the highest priority.