Function blocks
5.114
L_PosSequencer - sequence control
442
Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.114.3.3 Action type "Switching"
In order to switch digital output signals 25 actions of type "Switching" are available.
• Each action can set two selectable bits of the output signal dwDigitalOutputs to "0" or "1" inde-
pendently of each other.
Action call (entry in the sequence table)
with action number xxx = 001 ... 025
Parameter
The available actions 1 ... 25 are indicated via the subcodes 1 ... 25.
Parameter
Possible settings
Information
C04520/1...25
Output for A switching
0 Switching is deactivated.
1 Sequencer output 1
(Bit 0 of dwDigitalOutputs)
2 Sequencer output 2
(Bit 1 of dwDigitalOutputs)
... ...
32 Sequencer output 32
(Bit 31 of dwDigitalOutputs)
C04521/1...25
Signal state for A switching
0 Set bit to "0".
1 Set bit to "1".
C04522/1...25
Output for B switching
0 Switching is deactivated.
1 Sequencer output 1
(Bit 0 of dwDigitalOutputs)
2 Sequencer output 2
(Bit 1 of dwDigitalOutputs)
... ...
32 Sequencer output 32
(Bit 31 of dwDigitalOutputs)
C04523/1...25
Signal state for B switching
0 Set bit to "0".
1 Set bit to "1".
2 x x x