C02800, C02801, C02802 – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual
Page 644: C02803, C02800/1, C02800/2, C02801/1, C02801/2, 9400 highline | parameter setting & configuration
9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C02800
644
Firmware 1.37 - 09/2006
L
C02800
C02801
C02802
C02803
Parameter | Name:
C02800 | AINx: Input signal
Data type: INTEGER_16
Index: 21775
d
= 550F
h
Scaling: -16384 ≡ -100 %, +16383 ≡ +100 %
Display range
(min. value | unit | max. value)
-16384
16383
Subcodes
Information
C02800/1
Input signal of analog input 1
C02800/2
Input signal of analog input 2
;
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C02801 | AOUTx: Output signal
Data type: INTEGER_16
Index: 21774
d
= 550E
h
Scaling: -16384 ≡ -100 %, +16383 ≡ +100 %
Display range
(min. value | unit | max. value)
-16384
16383
Subcodes
Information
C02801/1
Output signal of analog output 1
C02801/2
Output signal of analog output 2
;
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C02802 | Status word dig. outputs
Data type: BITFIELD_32
Index: 21773
d
= 550D
h
Display of the hexadecimal value of the digital output port
• Important: All digital levels are indicated without considering the level logic. Internal signals are displayed as
well.
Display range
(min. value | unit | max. value)
0x00000000
0xFFFFFFFF
;
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C02803 | Status word dig. inputs
Data type: BITFIELD_32
Index: 21772
d
= 550C
h
Display of the hexadecimal value of the digital input port
• Important: All digital levels are indicated without considering the level logic. Internal signals are displayed as
well.
Display range
(min. value | unit | max. value)
0x00000000
0xFFFFFFFF
;
Read access Write access CINH PLC STOP No transfer COM MOT