1 setpoint inversion, 2 ramp generator, 1 setpoint inversion 11.3.4.2 ramp generator – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual
Page 272: 9400 highline | parameter setting & configuration
9400 HighLine | Parameter setting & configuration
Standard TAs
TA "Actuator – torque" | Torque setpoint conditioning
272
Firmware 1.37 - 09/2006
L
11.3.4.1
Setpoint inversion
[11-15] Setpoint inversion (schematic diagram)
Via the digital input DI3 the effective direction of the (bipolar) setpoint can be inverted, if
required.
r
Parameter setting: All parameters tab Category Actuator - torque Multiplexer
11.3.4.2
Ramp generator
[11-16] Ramp generator (schematic diagram)
In order to avoid setpoint step-changes the torque setpoint passes a ramp generator with
a parameterisable acceleration/deceleration and S-ramp time before it is transmitted to
the basic drive function "Torque follower".
r
Parameter setting: Tab Application parameter Dialog level Overview
M
Gain
Invert setpoint
LS_Torque...
M
Torque
setpoint
DI2
DI3
OUT
IN
Ramp generator
Status
machine
(basic drive
functions)
Torque setpoint
AIN1
v
F
Control inputs of the function
Signal configuration
Lenze setting
Control input
(Multiplexer parameters)
DigIn 3 Invert setpoint
C03003
M
Gain
Invert setpoint
LS_Torque...
M
Torque
setpoint
DI2
DI3
OUT
IN
Ramp generator
Status
machine
(basic drive
functions)
Torque setpoint
AIN1
v
F
Parameters
Lenze setting
Value Unit
C03550
Acceleration / deceleration time
0.010 s
C03551
S-ramp time
0.001 s