L
9.10
Limiter
The basic function "Limiter" monitors the travel range limits via limit switches and
parameterised software limit positions and can lead the drive to defined limit ranges when
being asked accordingly by the safety module.
See also:
Note!
In order that the basic function "Limiter", after being asked accordingly by the
safety module, can lead the drive to the defined limit ranges before the limits set
for the safety module are reached which stops the drive, the limit values for the
basic function "Limiter" must be set lower than the limit values for the safety
module!
Danger!
The safety is exclusively ensured by the safety module!
When the request for the safety function is cancelled, the drive restarts
automatically.
Ensure by external measures that the drive only starts after a confirmation
(EN 60204).