C00618, C00619, C00620 – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual
Page 596: C00625, C00635, Must, E set in, 9400 highline | parameter setting & configuration
9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00618
596
Firmware 1.37 - 09/2006
L
C00618
C00619
C00620
C00625
C00635
Parameter | Name:
C00618 | Number of CRC cycles
Data type: UNSIGNED_32
Index: 23957
d
= 5D95
h
Display range
(min. value | unit | max. value)
0
4294967295
;
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00619 | Resp. to max. motor current
Data type: UNSIGNED_32
Index: 23956
d
= 5D94
h
Response if the adjustable maximum motor current threshold (
) is exceeded.
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
2 Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
;
Read access ; Write access CINH PLC STOP No transfer COM ; MOT
Parameter | Name:
C00620 | Max. motor current threshold
Data type: UNSIGNED_32
Index: 23955
d
= 5D93
h
Threshold for maximum motor current monitoring
• The response when reaching the threshold can be selected in
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
A
3000.0 3000.0 A
;
Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 10
Parameter | Name:
C00625 | CAN behaviour in the case of error
Data type: UNSIGNED_8
Index: 23950
d
= 5D8E
h
Selection list
(Lenze setting printed in bold)
0 Pre-operational state
1 No state change
2 "Stopped" state
;
Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00635 | Resp. to new firmware of drive
Data type: UNSIGNED_32
Index: 23940
d
= 5D84
h
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
5 Warning
6 Information
;
Read access ; Write access CINH PLC STOP No transfer COM MOT