9400 HighLine | Parameter setting & configuration
Drive interface
Device states
4.5.3
State "Device is ready to switch on"
The controller is in this device state directly after the initialisation is completed and no DC-
bus voltage is applied yet.
r
The bus systems are running and the terminals and encoders are evaluated.
r
The monitoring modes are active.
r
The controller can be parameterised and device commands can be executed in a limited
way.
r
The application is basically executable.
r
The function of the user task can be used.
– Condition: The application has started (status display in
r
The basic drive functions cannot be used yet.
r
There are two options for a change from the "Device is ready to switch on" state to the
"Device is switched on" state:
– Auto restart enabled after mains connection (
= "1").
– Auto restart inhibited after mains connection (
= "0") and controller
inhibited.
Auto start option 1: Auto restart enabled after mains connection
r
The following figure shows the status change for the automatic start option 1 (Lenze
setting) as a function of the controller inhibit:
[4-12] State change when auto restart is enabled (C00142 = "1")
LED DRIVE READY
LED DRIVE ERROR
OFF
141: Device is ready to switch on
Controller pulses are inhibited
Controller pulses are enabled
n
o
With controller inhibit during power-on
Without controller inhibit during power-on
RFR
0
1
RFR
RFR
RFR
t
t
Initialisation
Switched on
Operation
Ready to switch on
Operation
Initialisation
Switched on
Ready to switch on