C00416, C00420, C00421 – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual
Page 583: C00422, C00427, 9400 highline | parameter setting & configuration

L
Firmware 1.37 - 09/2006
583
9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00416
C00416
C00420
C00421
C00422
C00427
Parameter | Name:
C00416 | Resolver error correction
Data type: UNSIGNED_32
Index: 24159
d
= 5E5F
h
Setting range
(min. value | unit | max. value)
Lenze setting
0
99999999 0
;
Read access ; Write access ; CINH PLC STOP No transfer COM ; MOT
Parameter | Name:
C00420 | Number of increments of the encoder
Data type: UNSIGNED_16
Index: 24155
d
= 5E5B
h
Setting range
(min. value | unit | max. value)
Lenze setting
1
16384 512
;
Read access ; Write access ; CINH PLC STOP No transfer COM ; MOT
Parameter | Name:
C00421 | Encoder voltage
Data type: UNSIGNED_16
Index: 24154
d
= 5E5A
h
Setting range
(min. value | unit | max. value)
Lenze setting
5.0
V
9.0 5.0 V
;
Read access ; Write access ; CINH PLC STOP No transfer COM ; MOT Scaling factor: 10
Parameter | Name:
C00422 | Encoder type
Data type: UNSIGNED_16
Index: 24153
d
= 5E59
h
Selection list
(Lenze setting printed in bold)
0 Incremental encoder (TTL signal)
1 Sin/cos encoder
2 Absolute value encoder (Hiperface)
3 Absolute value encoder (EnDat)
;
Read access ; Write access ; CINH PLC STOP No transfer COM ; MOT
Parameter | Name:
C00427 | TTL encoder signal evaluation
Data type: UNSIGNED_16
Index: 24148
d
= 5E54
h
Selection list
(Lenze setting printed in bold)
0 4x evaluation (A, B)
1 A:Increments B:Sign
2 Increments A:pos. B:neg.
;
Read access ; Write access ; CINH PLC STOP No transfer COM ; MOT