Introduction
Signal types &
scaling
2.3
Signal types & scaling
It is very helpful for the parameter setting & configuration of the controller to know the signal types and their scaling listed in the following table, which serve to
process physical sizes (e.g. a speed or position) in a function block configuration.
Signal type
Unit
Connection
symbol in
the FB editor
Resolution
Scaling
external ≡ internal
Range
Number of
decimal
positions
Identifier
suffix
Position
Increments
u
/ w
32 bits
1 motor revolution ≡ 2
16
increments
-2
31
... 2
31
-1 increments
3
_p
Speed
rpm
s
/ t
16 bits
15000 rpm ≡ 2
14
≡ 16384
± 30000.0 rpm
1
_v
x
32 bits
15000 rpm ≡ 2
26
≡ 67108864
± 480000.0 rpm
1
_s
Speed variation/time
rpm/s
v
32 bits
15000000 rpm/s ≡ 2
22
≡ 4194304
± 7.69 * 10
9
rpm/s
3
_x
Scaled signal
%
z
32 bits
100 % ≡ 2
30
≡ 1073741824
± 200.00 %
2
_n
y
16 bits
100 % ≡ 2
14
≡ 16384
± 199.99 %
2
_a
Control/status signal
{
1 bit
0 ≡ FALSE; 1 ≡ TRUE
0 / 1
0
Time
s
|
28 bits
0 ... 268435.456 s
3
Status word
|
32 bits
-2147483648 ... 2147483647
(0000 0000
hex
... FFFF FFFF
hex
)
0
Not standardised
|
O
Tip!
Only inputs/outputs of the same signal type (with the same
connection symbol) can be connected in the function block editor of
the »Engineer«.
Non-standardised inputs/outputs can be connected if the input and
output have the same resolution.