9400 HighLine | Parameter setting & configuration
Basic drive functions
Standard stop | Parameter setting
9.2.1
Parameter setting
r
Parameterisation dialog in the »Engineer«: Tab Application parameter Dialog level
Overview All basic functions Stop
r
Short overview of parameters for standard stop :
Parameter setting of stop
[9-2]
Deceleration time referred to the motor reference speed
[9-3]
Deceleration time referred to the current speed
[9-4]
S-shaped deceleration ramp through selection of a relative S-ramp time
Parameters
Information
Deceleration time for stop
S-ramp time for stop
Ref. for decel. time of stop
r
The deceleration time set in
for stop refers to a speed variation
from the motor reference speed
(
) to standstill, i. e. the
deceleration is constant.
n
t
C00011
C02610
r
is set = "1", the
deceleration time refers to the current
speed, i. e. the braking time is constant.
C02610
n
t
C00011
r
Through the entry of a S-ramp time in
an S-shaped deceleration
ramp for jerk reduction can be set. This
prolongs the total time to standstill by
the selected S-ramp time.
r
Braking time at motor reference speed
or
= "1":
n
t
C00011
n
t
C00011
C02612 = 0
C02612 = 1
C02610 + C02611
C02610 [s] C02611 [s]
+