C00597, C00598, C00599 – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual
Page 592: C00600, 9400 highline | parameter setting & configuration
9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00597
592
Firmware 1.37 - 09/2006
L
C00597
C00598
C00599
C00600
Parameter | Name:
C00597 | Resp. to motor phase failure
Data type: UNSIGNED_32
Index: 23978
d
= 5DAA
h
Response to release of motor phase failure monitoring
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
2 Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
;
Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00598 | Resp. to open circuit AIN1
Data type: UNSIGNED_32
Index: 23977
d
= 5DA9
h
Response if with master current at AIN1 and mode LifeZero (±4...±20 mA) the current is in the non permitted range
(-4...+4 mA).
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
2 Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
6 Information
;
Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00599 | Threshold motor phase failure
Data type: INTEGER_32
Index: 23976
d
= 5DA8
h
Threshold for motor phase failure monitoring
• The response when reaching the threshold can be selected in
Setting range
(min. value | unit | max. value)
Lenze setting
1.0
%
10.0 5.0 %
;
Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10
Parameter | Name:
C00600 | Resp. to DC bus overvoltage
Data type: UNSIGNED_32
Index: 23975
d
= 5DA7
h
Response to DC bus overvoltage
Selection list
(Lenze setting printed in bold)
1 Error
2 Fault
;
Read access ; Write access CINH PLC STOP No transfer COM ; MOT