Cpu: overtemperature [0x00770009, Heatsink: temperature sensor defective [0x0077000a, Motor: temperature sensor defective [0x0077000c – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual
Page 465: 9400 highline | parameter setting & configuration

L
Firmware 1.37 - 09/2006
465
9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
CPU: Overtemperature [0x00770009]
Heatsink: Temperature sensor defective [0x0077000a]
Inside the device: Temperature sensor defective [0x0077000b]
Motor: Temperature sensor defective [0x0077000c]
DC-bus capacitor: Temperature sensor defective [0x0077000d]
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CPU temperature higher than fixed limit temperature
(85 °C).
• Controller ambient temperature too high.
• Dirty fan or ventilation slots.
• Check control cabinet temperature.
• Clean filter.
• Clean controller.
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
;
None System fault : Fault Trouble Quick stop by trouble Warning locked ; Warning Information
Cause
Remedy
Encoder for heatsink temperature supplies undefined
values.
Check control cabinet temperature, maybe it is too low.
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
;
None System fault : Fault Trouble Quick stop by trouble Warning locked ; Warning Information
Cause
Remedy
Encoder for interior temperature supplies undefined
values.
Check control cabinet temperature, maybe it is too low.
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
;
None System fault : Fault Trouble Quick stop by trouble Warning locked ; Warning Information
Cause
Remedy
The signals of the connected encoder of the motor
temperature detection (resolver at X7 or encoder at X8)
are outside the defined operating range of detection.
• Check bonding of the encoder cable at the motor and
controller.
• Check selection of the motor temperature sensor in
and make sure that it complies with the
assembly in the motor.
• Possibly switch off temperature sensor monitoring
(
="0").
• If a PTC is in the motor, activate the monitoring of the
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
;
None System fault : Fault Trouble Quick stop by trouble Warning locked ; Warning Information
Cause
Remedy
Encoder for capacitor temperature supplies undefined
values.
Check control cabinet temperature, maybe it is too low.