8 quick stop, Quick stop, C 279) – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual
Page 279: Quick stop (c 279), 9400 highline | parameter setting & configuration, Standard tas ta "actuator – torque" | quick stop
L
Firmware 1.37 - 09/2006
279
9400 HighLine | Parameter setting & configuration
Standard TAs
TA "Actuator – torque" | Quick stop
11.3.8
Quick stop
[11-22] Basic function "Quick stop" (schematic diagram)
r
The quick stop function can be activated as follows in the Lenze setting:
– By setting the digital input DI1 to LOW level.
– By a master control via the port LPortAxisIn1:
By setting bit 3 of the bit-coded axis control word.
r
Parameter setting: Tab Application parameter Dialog level Overview Quick stop
O
Tip!
Detailed information on quick stop can be found in chapter "Basic drive functions"
subchapter "
The basic function "Quick stop" brakes the
drive to standstill within the deceleration
time set for the quick stop function after a
corresponding request independent of the
setpoint selection.
If the quick stop is deactivated, the defined
torque is available again, as the case may
be, an acceleration via the set acceleration
time of the speed limit value is effected.
LS_ManualJog
n
t
и
з
LS_Brake
n
t
LS_Limiter
n
t
LS_Quickstop
STOP
LS_Torque...
M
Torque
setpoint
n
t
LS_Stop
internal
status machine
DI2
DI6
DI7
DI8
DI1
Status
machine
(basic drive
functions)
Basic drive functions
M
v
F
и
з
Parameters
Lenze setting
Value Unit
Quick stop deceleration time
0.000 s
Quick stop S-ramp time
0.00 %
Reference for deceleration time "Quick stop"
Control inputs of the function
Signal configuration
Lenze setting
Control input
(Multiplexer parameters)
DigIn 1 Activate quick stop 1
C03135/1
Axis control word
bit 03
Activate quick stop 2
C03135/2
FALSE Activate quick stop 3
C03135/3