Chapter 1 Specifications Check

1.2.1 XSEL-R/S Controller

Type

38

[2] Power Capacity and Heating Value

Calculate the Power Capacity and Heating Value using the following formulas.

Rated Power Capacity [VA]=Total Capacity of Motor Power [VA]+Total of the power

consumption at the control part [VA]

Heating Value [W]=Total Output Loss [W]+(Total of internal power consumption [VA]

×0.7(Efficiency)×0.6(Power factor))

Select the motor power capacity [VA] from Table 1. However, please note that the motor

power capacity at the acceleration and deceleration is 3 times higher at most. (2 times

higher max. for motor wattage 600W)

Figure out the total of the power consumption at the control part [VA] with the total of

power of the actually mounted components � quantity, by selecting the applicable ones

from Table 2 Control Power Source (Internal Consumption and External Consumption).

To calculate the sum total of output loss [W], refer to the “Output Loss” column in Table 1

below and select the values corresponding to the output losses of each connected

actuator.

For the inner power demand (VA) for calculating the heating value (W) in the control unit,

select the components which are being placed, from the columns of Control Power

Supply (Internal Consumption) and External Power Supply (Internal Consumption) in

Table 2 and calculate it using the formula “Power {SYMBOL} Quantity of the Placement

Component”

Table 1 Motor Volt Amperage of Actuator and Output Loss

Wattage of Actuator Motor

Motor Power Capacity [VA]

Output loss = Heat Generation [W]

20

26

1.58

30

46

2.07

60

138

3.39

100

234

6.12

150

328

8.30

200

421

9.12

40

796

19.76

600

1164

27.20

750

1521

29.77

100 (Linear Actuator

LSAS-N10SS)

379

37

200 (Linear Actuator

LSAS-N15SS)

486

37

200 (Linear Actuator

LSAS-N15HS)

773

39