Chapter 7

Troubleshooting

7.3 Error List (MAIN application)

449

In the panel window, the error numbers follow E in the display.

Error

No.

Error name

Description, action, etc.

C02 Executable program count over

error

Execution requests were received for programs exceeding

the number that can be executed simultaneously.

C03 Non-registered program

specification error

A number not yet registered among program Nos. 1 to 128

was specified via an I/O or in a program.

C04 Program entry point non-detection

error

A request was made to execute a program number for

which no program steps are registered.

C05 Program first-step BGSR error

The program specified for execution starts with BGSR.

C06 Executable step non-detection

error

The program specified for execution does not contain

executable program steps.

C07 Subroutine non-definition error

The subroutine specified for call is not defined.

C08 Subroutine duplicate-definition

error

The same subroutine number is defined at multiple

locations.

C0A Tag duplicate-definition error

The same tag number is defined at multiple locations.

C0B Tag non-definition error

The tag specified as the jump destination of a GOTO

statement is not defined.

C0C DW/IF/IS/SL pair-end mismatch

error

The branching command syntax is invalid.

Correspondence with the last appearing branching

command is invalid when EDIF, EDDO or EDSL is used.

Check the correspondence between IF/IS command and

EDIF, DO command and EDDO or SLCT command and

EDSL.

C0D DW/IF/IS/SL no pair-end error

EDIF, EDDO or EDSL is not found.

Check the correspondence between IF/IS command and

EDIF, DO command and EDDO or SLCT command and

EDSL.

C0E BGSR no pair-end error

There is no EDSR for BGSR, or no BGSR for EDSR.

Check the correspondence between BGSR and EDSR.

C0F DO/IF/IS over-nesting error

The number of nests in a DO or IF/IS command exceeds

the limit value.

Check for excessive nesting or branching out of or into the

syntax using a GOTO command.

C10 SLCT over-nesting error

The number of nests in a SLCT command exceeds the

limit value.

Check for excessive nesting or branching out of or into the

syntax using a GOTO command.

C11 Subroutine over-nesting error

The number of nests in a subroutine exceeds the limit

value.

Check for excessive nesting or branching out of or into the

syntax using a GOTO command.

C12 DO/IF/IS under-nesting error

The EDIF or EDDO position is invalid.

Check the correspondence between IF/IS command and

EDIF or DO command and EDDO, or branching out of or

into the syntax using a GOTO command.

C13 SLCT under-nesting error

The EDSL position is invalid.

Check the correspondence between SLCT and EDSR, or

branching out of or into the syntax using a GOTO

command.

C14 Subroutine under-nesting error

The EDSR position is invalid.

Check the correspondence between BGSR and EDSR, or

branching out of or into the syntax using a GOTO

command.

O

pe

ra

tio

n-

ca

nc

el

la

tio

n

le

ve

l e

rro

rs

C15 SLCT next-step command code

error

The program step next to SLCT must be WHEQ, WHNE,

WHGT, WHGE, WHLT, WHLE, WSEQ, WSNE, OTHE or

EDSL.