beautypg.com

Transference of pio signal between controllers, Plc timer setting (reference) – IAI America XSEL-S User Manual

Page 18

background image

10

6. Transference of PIO Signal between Controllers

Please note the following when conducting transference of PIO signal between controllers.

To certainly transfer the signal between controllers with different scan time, it is necessary to

have longer scan time than the one longer than the other controller. To ensure to end the

process of signal safely, it is recommended to have more than twice as long as the longer

scan time at least.

�Operation Image

Also, if one tries to read the signal that is being re-written by the other, the signal may be read wrong.

Make sure to read the signal after the rewriting is complete. (It is recommended to have more than 2

scan periods to wait.) Make sure not to have the output side to change the output until the other side

completes the reading. Also, a setting is made on the input area not to receive the signal less than a

certain time to prevent a wrong reading of noise. This duration also needs to be considered.

Note1 Because this controller performs two or more processing works including program execution and

error processing, in addition to I/0 processing, the scan time is not fixed.

7. PLC Timer Setting (Reference)

Do not have the PLC timer setting to be done with the minimum setting.

Setting to “1” for 100msec timer turns on at the timing from 0 to 100msec while 10msec timer

from 0 to 10msec for some PLC.

Therefore, the process same as when there is no timer set will be conducted and a failure may

be occurred.

Set “2” as the minimum value for the setting of 10msec timer and when setting to 100msec,

use 10msec timer and set to “10”.

PLC

(e.g. scan time is 20msec)

Output

Process

Input

Process

As shown in the diagram, the input and output

timings of two devices that have different scan

time do not match, when transferring a signal.

There is no guarantee that PLC would read the

signal as soon as this controller signal turns

on.

In such a case, make the setting to read the

signal after a certain time that is longer than

the longer scan time to ensure the reading

process succeeds on the PLC side. It is the

same in the case this controller side reads the

signal.

In such a case, it is recommended to ensure 2

to 4 times of the scan time for the timer setting

margin.

It is risky to have the setting below the scan

time since the timer is also processed in the

scan process.

In the diagram, PLC can only read the input

once in 20msec even though this controller

output once in 1msec.

Because PLC only conducts output process

once in 20msec, ASEP/PSEP identifies the

same output status for that entire time period.

This controller

(scan time some msec)

(Note1)

This manual is related to the following products: